Fronius IG Plus |
3.0-1UNI |
3.8-1UNI |
|
Input data |
|
|
| Recommended PV-Power (Wp) |
2500-3450 |
3200-4400 |
| MPPT-Voltage range |
230 - 500 V |
230 - 500 V |
Max. Input voltage range (at 1000 W/m² 14°F (-10°C) in open circuit operation) |
600 V |
600 V |
| Nominal Input Current |
8.3A |
10.5 A |
| Max. usable Input Current |
14.0 A |
17.8 A |
| Admissible conductor size (DC) |
No. 14-6 AWG |
|
Output data |
|
|
| Nominal output power (PAC nom) |
3000 W |
3800 W |
Max. continupous output power 104°F (40°C) 208 V / 240 V / 277 V |
3000 W |
3800 W |
| Nominal AC output voltage |
208 V / 240 V / 277 V |
|
Operating AC voltage range (default) 208 V 240 V 277 V |
183 - 229 V (-12 / +10 %) 211 - 264 V (-12 / +10 %) 244 - 305 V (-12 / +10 %) |
| |
|
|
Maximum continuous output current 208 V 240 V 277 V |
14.4 A 12.5A 10.8A |
18.3 A 15.8A 13.7A |
| Admissible conductor size (AC) |
No. 14 - 4 AWG |
| Max. continuous utility back feed current |
0 a |
| Nominal frequency |
60 Hz |
| Operating frequency range |
59.3 - 60.5 Hz |
| Total harmonic distortion |
< 3 % |
| Power factor |
1 |
|
General data |
|
|
| Max. Efficiency |
96.2 % |
CEC Efficiency 208 V 240 V 277 V |
95.0 % 95.5 % 95.5 % |
95.0 % 95.5 % 95.5 % |
| Consumption in standby (night) |
<1 W |
| Consumption during operation |
8 W |
| Cooling |
Controlled forced ventilation, variable fan speed |
| Enclosure Type |
NEMA 3R |
| Unit Dimensions (W x H x D) |
17.1 x 24.8 x 9.6. in. |
| Power StageWeight |
31 lbs. (14 kg) |
| Wiring Compartment Weight |
24 lbs. (11 kg) |
| Admissing ambient operating temperature |
-4 ... 122°F (-20 ... + 50°C) |
| Compliance |
UL 1741-2005, IEEE1547-2003, IEEE 1547.1, ANSI/IEEE C62.41, FCC Part 15 A&B, NEC Article 690, C22. 2 No. 107.1-01 (Sept. 2001) |
|
Safety equipment |
|
|
| Ground fault protextion |
Internal GFDI (Ground Fault Detector/Interrupter); in accordance with UL 1741-2005 and NEC Art. 690 |
| DC reverse polarity protevtion |
Internal diode |
| Islanding protection |
Internal; in accordance with UL 1741-2005, IEEE 1547-2003 and NEC |
| Over temperature |
Output power derating / active cooling |